These changes obtain feasibility for the Eastern base case. The first four changes (by branch ID) achieve general feasibility with the scaled-up generation capacity: ensuring that there is no conflict between generator Pmins and their associated transformer ratings (tested in Scenario #307). The rest of the changes achieve feasibility through the summer months without any load curtailment, and were tested in Scenario #308 and #309. For each branch, the
rateA
field is multiplied by a scale factor, and thex
field is divided by the scale factor (as branches are scaled in the change_table).See: https://github.com/intvenlab/RenewableEnergyProject/issues/193